Honeywell VisionPRO® IAQ Installation Manual

Honeywell VisionPRO IAQ Specifications

Below is a product description and manual description of the Honeywell VisionPRO IAQ.

The Honeywell VisionPRO IAQ thermostat is a device designed to control and regulate heating, ventilation and air conditioning (HVAC) systems in residential and commercial buildings. It is mainly available in the US market.

A popular feature of the VisionPRO IAQ thermostat is its ability to control indoor air quality, hence the "IAQ" in its name. It can monitor and adjust humidity levels to maintain a comfortable and healthy environment. This is especially helpful for people with allergies or breathing problems. In terms of installation, the VisionPRO IAQ thermostat is compatible with a variety of HVAC systems, including single-stage, multi-stage, and heat pump systems. It offers different scheduling options for weekdays and weekends, allowing users to adjust the temperature settings based on their needs and preferences. The flashlight has a large touch screen on the back that is easy to read and navigate. It also has a programming interface that simplifies the menu, making it user-friendly for both home owners and professional users. In addition, the VisionPRO IAQ Thermostat comes with advanced features such as seven-day scheduling options, vacation hold, and easy-to-use scheduling capabilities. It also has a programmable fan control feature, allowing users to adjust fan settings to optimize airflow and air circulation in their space. Overall, the Honeywell VisionPRO IAQ Thermostat provides reliable and efficient control of the HVAC system, focusing on maintaining indoor air quality and comfort. The difference between its users and its style makes it a popular choice among homeowners and businesses.

Honeywell VisionPRO® IAQ Special function

  • Auto Discover: Setup functions set to “E” (Auto Discover) will be configured automatically, based on information sent from connected equipment. When using Auto Discover, verify that the discovered value is correct. If it is not, the equipment is not communicating the information, and you must change settings manually.
  • Adaptive Intelligent Recovery (Setup Function 0530): Allows the thermostat to “learn” how long the furnace and air conditioner take to reach programmed temperature settings, so the temperature is reached at the scheduled time.
  • Compressor Protection (Setup Function 0580): Forces the compressor to wait a few minutes before restarting, to prevent damage. During this time, the message “Wait” flashes on the display.
  • Southern Away Dehumidification Control (Setup Functions 0390-0394): This feature is useful for homes in southern climates. It allows humidity control when the the home is unoccupied for long periods during the hot/humid season. You can control temperature (Function 0393) and dehumidification (Function 0394) while away. You can control humidity with a dehumidifier or a cooling system (Function 0379). If a cooling system is used, humidity is controlled by cooling indoor air to the Low Limit Temperature (Function 0392). When the desired humidity is reached, the system will maintain the temperature you select in Function 0393.
  • Heat Pump Control — Electric Backup (Setup Functions 0350-0360): If an outdoor temperature sensor is installed, select a compressor lockout temperature (Function 0350). Below this temperature, only electric heat operates. Also select an auxiliary lockout temperature (Function 0360). Above this temperature, only the compressor operates. Between these temperatures, both heat sources operate.
  • Heat Pump Control — Fossil Fuel Backup (Setup Function 0345): Option 0 (Balance point only): If outdoor temperature is above balance point (Function 0350), only the compressor operates. Below this temperature, only backup heat operates.
    • Option 1 (Balance point + 2°F droop): As above, but backup heat is activated if room temperature drops by 2°F (compressor is deactivated).
    • Option 2: (Balance point/Aux Heat +2°F droop): Compressor works only above auxiliary lockout temperature, backup heat works only below balance point, 2°F droop between temperatures. If temperature is not reached in a reasonable time, set the upstage timer (Function 0346). After the designated time, the compressor will be deactivated and the system will switch to backup heat.
  • Ventilation Control (Setup Functions 0400-0406): If the system includes a self-powered ventilation unit (Function 0400), the home can be ventilated on demand, or ventilated automatically if high humidity is detected while in heating mode (Function 0406).

Readmore and Download Honeywell VisionPRO® IAQ Installation Manual PDF