Honeywell Thermostat L4006 User Manual

These boiler-mounted, immersion type controllers operate in response to temperature changes in hydronic heating systems. L4006A breaks the circuit on a temperature rise to the control setting. It is used for high limit or low limit control.
When used as a controller or as a low limit, a separate high limit must be used. L4006B makes the circuit on a temperature rise. It is used as a circulator controller, delaying circulator operation when boiler water temperature is below the control setting.

L4006E,H includes a trip-free manual reset switch. These models are designed to break the control circuit whenever the temperature of the controlled medium reaches the high limit setting. A reset button on the front of the case must be pressed to re-establish the control circuit. L4006H also includes bracket and clamp for surface mounting on pipe or tank. A plastic bag of heat-conductive compound is included with the L4006A,B,E AquastatÆ Controllers for use when the sensing bulb is inserted into a well designed for a large bulb than the one used on the L4006A,B,E. A 124904 Well Adapter, for use on old wells that do not fit the L4006A,B,E immersion well clamp, can be ordered; see form 68-0040, Wells and Fittings for Temperature Controllers.. A setting stop is included to prevent setting above a desired temperature on limit. If a well adapter or other accessories are needed, refer to form 68-0040, Wells and Fittings for Temperature Controllers, for part numbers and ordering information.

A type of water heater that works in response to temperature changes in a hydronic heating system.

The L4006A breaks the circuit when the temperature rises to the control setting. It is used for high or low control. When used as a control or low limit, a different high limit will be used. L4006B operates the circuit in the event of temperature rise. It is used as a distributor, delaying the operation of the distributor when the hot water temperature is below the control setting. L4006E,H includes a non-triggered manual reset switch. These models are designed to close the control circuit whenever the controlled fluid reaches a critical point. The reset button on the front of the case must be pressed to reset the control circuit. The L4006H also includes a bracket and clamp for mounting on a pipe or tank.

Honeywell Thermostat Spesification

TRADELINE models are selected and packaged to provide ease of stocking, ease of handling, and maximum replacement value. Specifications of SUPER TRADELINE and TRADELINE controls are the same as those of standard models except as noted below.

  • SUPER TRADELINE Model: L6006A Aquastat Controller.
  • SUPER TRADELINE Features: SUPER TRADELINE package with cross reference label and special instructions. Factory-set stop at 240° F (116° C). Vertical or horizontal mount. Tube of heat-conductive compound.
  • Insulation: 1-1/2 in. to 3 in. (38 mm to 76 mm).
  • TRADELINE Models: L4006A,B,E; L4008E; L6006C; L6008A Aquastat Controllers.
  • TRADELINE Features Available: TRADELINE package with cross reference label and special instructions. Some TRADELINE models include immersion well. Factory-set stops at 180° F, 240° F, or 250° F (82° C, 116° C, or 121° C). Vertical or horizontal mount. Tube of heat-conductive compound. Insulation depths of 1-1/2 in. or 3 in. (38 or 76 mm).
  • Electrical Ratings (A): Models with 2° F (1° C) fixed differential:

     

    120 Vac

    240 Vac

    Full Load

    2.6

    1.3

    Locked Rotor

    15.6

    7.8

    Models with 5° F (3° C) fixed differential or 5° F to 30° F (3° C to 17° C) adjustable differential:

     

    110/120 Vac

    200/240 Vac

    277 Vaca

    Full Load

    8.0

    5.1

    4.2

    Locked Rotor

    48.0

    30.6

    25.2

    Millivoltage

    0.25 at 0.25 to 12 Vdc

    a L6008G only.

  • Switching:

    • L4006, L4007, L4008: Spst.

    • L6006, L6007, L6008: Spdt (breaks R-B and makes R-W on temperature rise at setpoint).

  • Pressure Rating: Capillary Bulb (Direct Immersion): 200 psi (1379 kPa). Immersion Well: 255 psi (1758 kPa).

  • Sensing Bulb Material: Copper.

  • Sensing Bulb Fill: Liquid—toluene or silicone oil.

  • Sensing Bulb Dimensions: 2-7/8 in. (73 mm) long, 3/8 in. (10 mm) diameter.

  • Wiring: Screw terminals.

  • Maximum Ambient Temperature: 150° F (66° C).

Honeywell Thermostat L4006 Feature

  • L4006, 7, and 8 provide Spst switching for high or low limit or circulator control.
  • L4006G includes two Spst switches that provide high limit and circulator control.
  • L4006,7; L6006,7 models are available for insertion in: vertical or horizontal immersion well, vertical or horizontal direct immersion, and surface mounting.
  • L4008, L6008 include remote bulb for mounting controller at a location away from the sensing element.
  • Totally enclosed Micro Switchô snap-acting switches operate on temperature rise to set point.
  • Models calibrated for high limit use are also suitable for low limit control if a separate high limit controller is used.
  • Visible control point scale and external adjustment screw, permit easy setting.
  • Remote bulb models may be used to sense air temperature in ducts and in outside air sensing applications.

Readmore and Download Honeywell L4006 Aquastat Controllers Manual