Honeywell T7200D,E, T7300D,E,F and Q7300 Manual

The T7200, T7300 Thermostats and Q7300 Subbases control 24 Vac commercial single zone heating, ventilating and air conditioning (HVAC) equipment. In addition, the Q7300H Communicating Subbase can communicate schedule information and system instructions to other devices in a LONWORKS® network.

Honeywell T7200D,E, T7300D,E,F and Q7300 FEATURES

All Models:

  • 7-day programming.
  • Two Occupied and two Unoccupied periods per day.
  • Individual heat and cool setpoints available for Occupied and Unoccupied periods.
  • Proportional plus Integral (P+I) control eliminates temperature fluctuations.
  • Intelligent Recovery ® control automatically optimizes equipment start times based on building load.
  • Intelligent Fan™ feature energizes fan continuously in the Occupied periods. Fan can also be configured for conventional heat or electric heat fan operation.
  • Automatic or manual changeover models available.
  • Universal Versaguard™ Thermostat guards available.
  • Convenient overrides allow temporary setpoint changes.
  • Keypad lockout available.

Honeywell T7200D,E, T7300D,E,F and Q7300 SPECIFICATIONS

  • Electrical Ratings: 24 Vac, 50/60 Hz. 20 to 30 Vac, 50/60 Hz.
  • Batteries: No batteries required.
  • Auxiliary Heat and Emergency Heat Indication: Thermostat display indicates when Auxiliary Heat or Emergency Heat are activated.
  • Loss of Power: The thermostat maintains programmed times and temperatures for the life of the product. The clock and day information is retained for a minimum of two hours.
  • Light Emitting Diodes (LED): Two user-defined LED (not available on Q7300H). Two defined (CHECK and MAINTENANCE) LED on select models.
  • System Current Draw: 6 VA maximum at 30 Vac, 50/60 Hz
  • Temperature. Ratings: Operating Ambient: 40°F to 110°F (4°C to 43°C).
  • Shipping: -30°F to +150°F (-34°C to +65°C). Display Accuracy: ±1°F (±0.5°C).
  • Setpoint: Range: 45°F to 95°F (7°C to 35°C). Deadband: 2°F (1°C).

Honeywell T7200D,E, T7300D,E,F and Q7300 Product Data

T7200D,E Thermostats:

  • Use on single-stage conventional (T7200D) or heat pump (T7200E) applications.

T7300D,E Thermostats:

  • Use on multistage conventional (T7300D) or heat pump (T7300E) applications.
  • Models available with remote sensor capability.

T7300F Thermostats:

  • Use on single-stage or multistage system in conventional or heat pump applications.
  • Auxiliary contacts on Q7300 can be used to interface with C7400/W7459 Economizer System for total integration of rooftop control.
  • Remote temperature sensors available for use with all models.
  • Different levels of keypad lockout available. Q7300 Subbase:
  • Use with T7300D,E,F Thermostats.
  • Auxiliary contacts can be used to interface with C7400/W7459 Economizer System for total integration of rooftop control.
  • When used with the T7300F (revision 4 or later), the Q7300H communicates with other network devices.
  • Q7300L two stages of heat control ML7984 and V5011/ V5013 valve: stage 1 opens valve 40%; stage 2 100%.
  • Q7300L provides two-speed fan control:
    • Low: heat and occupied fan.
    • High: cooling.

Readmore and Download Honeywell Honeywell T7200D,E, T7300D,E,F and Q7300 Manual

Title

: Honeywell T7200D,E, T7300D,E,F and Q7300 Manual

Format

: PDF

Pages

: 36 Pages

Language

: English

File Size

: 1 MB