Honeywell MICRONIK 200 R7426A User Manual

GENERAL

This document provides instructions and procedures for installing and starting up the Micronik 200 R7426A,B,C controllers. No special tools are required for mounting and installation. The user interface and liquid-crystal display allow accurate and easy parameter setting and output adjustment.

BEFORE INSTALLATION NOTE

  • Visually inspect equipment for shipping damage. Report any damage to the appropriate Honeywell representative.
  • Refer to job drawings for specific installation information and mounting location.
  • Verify the controllers will be adequately separated from the main power supply, relays, or other equip- ment which can possibly generate electromagnetic interference.
  • Verify that the ambient temperature and the humidity at the controllers will not exceed 0...50°C (32...122°F) and 5 to 95% rh.
  • Use shielded wiring in areas with high EMI.
  • All wiring should be separated from power lines by at least 150 mm (6’’).
  • Do not install controllers near frequency converters or other high-frequency sources.

MOUNTING

The controllers can be mounted in an electric cabinet or other suitable enclosure. They are suitable for back panel, DIN rail, wall, or front panel mounting. The corresponding mounting sequence, as well as dimensions and panel cut-out, are
illustrated in the mounting instruction sheet EN1B-0202GE51 supplied with the controllers. If the compensation sensor signal (T3) is received from another controller (parallel connection of compensation sensor inputs), the jumper W303 has to be cut before mounting the controller (see Fig. 2). This disconnects the sensor from the internal power supply. 

WIRING

Screwless type, spring loaded terminals are provided on the controllers for panel and field wiring. These terminals are suitable for solid conductors as well as tinned or with multicore cable end, stranded wires up to 1.5 mm2 . To make a termination, push the wire into the terminal or insert a small screwdriver from the front of the controller into the spring-release hole and insert the wire. Check for proper connection by short pull on the wire.

Table 1. Terminal Connection

controller to CPA/SPA potentiometer

R7426A,B,C

T7412B1016

T7412B1057/1008 T7412C1030/1006

T7412B1024 T7412B1040

terminal 2

terminal 4

terminal 4

terminal 4

terminal 4

terminal 5

terminal 6

terminal 5+6

R7426A,B,C

43193982-001

-

-

terminal 2

terminal 1

-

-

terminal 4

terminal 3

-

-

 

Table 2. Wire Dimensions

wiring run

type of wires

length max.

1.0 mm2

1.5 mm2

from controller to all input and output devices

local standard

 

100 m

 

150 m

POWER SUPPLY AND GROUNDING

  1. Refer to job drawings and verify correct supply voltage to transformer (230 Vac) and controller (24 Vac).
  2. Connect line power conductors to transformer primary. Line power must be supplied from a breaker panel with dedicated controller circuit. Do not turn the line power on until all wiring has been checked against job drawings.
  3. Connect transformers 24 Vac secondary to the controller terminals 18 and 19. Connect one conductor to terminal marked 24 V and the other to terminal marked 24 V. If controllers are interconnected all terminals 19 must be connected to the same potential 24 V level.
  4. Do not connect the secondary side of the transformer to the installation ground.

Honeywell MICRONIK 200 R7426A User Manual

Wiring should be done only according to the actual job wiring diagrams or wiring diagrams shown in the mounting instruction sheet EN1B-0202GE51. The wiring to the CPA/SPA potentiometers is described in Table 1. All wiring must conform to applicable codes, ordinances, and regulations. The maximum allowed wiring length per wire size are shown in Table 2.

Fig. 2. Parallel Connection of Compensation Sensor T3
Table 3. Jumper States

jumper1)

state

description

 

W303

closed

T3 supplied by this controller

open

T3 supplied from another controller

1) Default jumper position = closed. Cut (open) jumper W303 only if the T3 input is fed from another controller (parallel connection, max. six devices). This disconnects the T3 input from the internal power supply

 