Zone Panel Professional Installation Guide

Honeywell HZ221 TrueZONE Table of Content

  • Specifications and Accessories
  • Installation
  • Wiring
  • Operation
  • Warranty

Honeywell HZ221 TrueZONE Spesification

Input Ratings:

Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more.
 

Current Draw:

Zone Panel: 6.25 VA max. All VA specifications at 24 VAC.

Wiring:

18–20-gauge solid (not stranded) wire.

Humidity Ratings:

5% to 90% RH non-condensing.

Temperature Ratings:

Shipping: -20° to 150°F (-29° to 66°C)
Operating: -40° to 165°F (-40° to 74°C)
Dimensions:
See below.
Emissions:
Complies with FCC Class B, part 15 requirements.

Honeywell HZ221 TrueZONE Dimension

Specifications and accessories

RECOMMENDED THERMOSTATS, DAMPERS, AND ACCESSORIES

The following are suggested thermostats, dampers, and accessories for use with the TrueZONE panel.

Table 1. Recommended Thermostats

System

Non-Programmable

Programmable

Heat Pump

TH3210D, TH5220D, TH5320U

TH4210D, TH6220D, TH8220U, TH8321U,

YTH9421C

Note: These thermostat models all have different four- digit suffixes. All versions of the model numbers listed above will work with the applications they're listed for.

Table 2. Recommended Dampers.

Type

Honeywell Damper

Round

Rectangular

Zone

Spring-open/ power-closed

ARD

ZD

Zone

Power-open/ power-closed

MARD/ RRD

For recommended dampers call the Honeywell Zoning Hotline at

1-800-828-8367.

Bypass

Static pres- sure regulat- ing damper

SPRD

SPRD

Table 3. Maximum Dampers.*

Ambient Temp.

Maximum Damper VA per Zone

100°F (38°C)

28.8

160°F (71°C)

16.8

* Use an SDCR (Slave Damper Control Relay) for addi- tional dampers.

Maximum dampers per panel is limited by transformer size.

Ensure transformer is large enough to power the panel (6.25 VA) and dampers.

Table 4. Accessories.

Accessory

Description

40 VA transformer*

AT140A1042*

75 VA transformer

AT175A1008

Discharge Air Temperature Sensor (DATS)*

DATS C7735A1000*

SDCR

Slave Damper Control Relay

* Included in HZ221K kit.

Installation

  1. Mount the HZ221 TrueZONE panel near the HVAC equipment; locate it on a wall, stud, roof truss, or cold-air return. NOTE: The HZ221 TrueZONE panel can be mounted in any orientation; level it for appearance onlyhoneywell hz221 truezone Installation
  2. Separate the zone panel cover from the base, and use the base as a template to drill mounting holes. 2 Attach the base to the wall, stud, roof truss, or duct with appropriate screws (not included).honeywell hz221 truezone Installation
  3. Install thermostats using instructions provided with thermostats. Connect thermostat to zone panel. To connect wire to the panel, strip approximately 1/4 in. of insulation and push wire into terminal. To release wire, press the button on top of the terminal. In retrofit applications, trim end of wire if not straight. If the thermostat has separate E and Aux terminals, install a jumper between the two terminals.honeywell hz221 truezone Installation
  4. Install dampers using instructions provided with dampers. Connect dampers to zone panel. NOTE: Multiple dampers can be wired in parallel.honeywell hz221 truezone Installation
  5. Connect DATS as shown.honeywell hz221 truezone Installation
  6. Connect equipment as shown. The DS/BK terminal is used with a variable-speed fan. Connect to the DS, BK, or ODD terminal on the furnace equipment. When only one zone calls for heat, cool, or fan, the DS/BK terminal operates the fan at low speed to reduce airflow.honeywell hz221 truezone Installation
  7. Connect transformer as shown.honeywell hz221 truezone InstallationThe following diagram is an overall view of wiring for a heat pump system as depicted in steps 3–7.

honeywell hz221 truezone Installation

Operation

The HZ221 TrueZONE panel contains an LED display that communicates system and zone status. The LEDs indicate the following information.

Table 5. LED Operation.

LED

Description

HEAT

Solid when in heat.

Blinking when DATS temperature exceeds 120°F (49°C) and calling for heat pump only.

Blinking when DATS temperature exceeds 160°F

(71°C) and calling for heat pump and auxiliary heat. At 150°F (66°C), auxiliary heat is disabled.

COOL

Solid when in cool. Blinking when 45°F (7°C) DATS low limit mode has been reached.

FAN

Solid when in operation.

PURGE

Solid when in purge (lasts 2 minutes at power-up and after a call for heat or cool). Blinking when the DATS sensor has failed, or the wires are shorted or open. Will blink for 3 minutes at power-up if DATS is not present.

ZONE 1, 2

Solid green when open or opening. Solid red when closed or closing.

Blinking amber when there is a damper or thermo- stat short circuit (circuit breaker trip).

EM HEAT

Solid when in Em Heat mode.