Honeywell Home RedLINK FocusPRO Thermostats Technical Reference Manual

TECHNICAL REFERENCE MANUAL

2–3 Zones

System Type:

1–2 Stage Furnace + 1–2 Stage Cooling...................................................................................... Option A. Page 2

Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat .......................................... Option A. Page 2

2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat .................................................... Option B. Page 3

Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ...................................... Option C. Page 4

4 Zones

System Type:

1–2 Stage Furnace + 1–2 Stage Cooling ............................................................................................ Option B. Page 2

Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat .......................................... Option B. Page 2

2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ..................................................... Option B. Page 2

Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ...................................... Option C. Page 4

5–32 Zones

System Type:

1–2 Stage Furnace + 1–2 Stage Cooling ............................................................................................ Option D. Page 4

Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat .......................................... Option D. Page 4

2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ..................................................... Option D. Page 4

Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ...................................... Option D. Page 4

Prestige Thermostats for All Zones

2–3 Zones

System Type:

1–2 Stage Furnace + 1–2 Stage Cooling....................................................................................... Option E. Page 6

Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat .......................................... Option E. Page 6

2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ......................................................Option F. Page 6

Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ......................................Option G. Page 6

4 Zones

System Type:

1–2 Stage Furnace + 1–2 Stage Cooling .............................................................................................Option F. Page 6

Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ...........................................Option F. Page 6

2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ......................................................Option F. Page 6

Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ......................................Option G. Page 6

RedLINK VisionPRO Thermostats

RedLINK VisionPRO Thermostats..................................................................................................................... Page 8

Zoning without IAQ Control................................................................................................................................ Page 9

EIM to Zone Panel Wiring Diagrams.............................................................................................................. Page 10

IAQ CONTROL FROM ZONE 1 STAT

Option A: 2–3 Zones

Table 1. 1–2 Stage Furnace + 1–2 Stage Cooling or Single Stage Heat-Pump + Electric Heat-Strips for Auxiliary Heat. No Dual Fuel.

Parts list

Description

Quantity

1. HZ322K zone panel kit

Includes HZ322 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer

1

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM. (Different kits can also include accessories such as a RedLINK Internet gateway.)

1

3. YTH6320R1023

Includes TH6320R1004 wireless programmable FocusPRO thermostat and THM4000R1000 adapter

1

4. TH6320R1004

Wireless thermostat for zone 3 (not needed for 2 zone system)

0–1

5. Appropriate zone dampers and by-pass damper for the application

 

Option B: 2–4 Zones

Table 2. 1–3 Stage Furnace + 1–2 Stage Cooling, or 1–2 Stage Heat-Pump + Electric Heat-Strips for Auxiliary Heat.

Parts list

Description

Quantity

1. HZ432K zone panel kit

Includes HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer

1

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM. (Different kits can also include accessories such as a RedLINK Internet gateway.)

1

3. YTH6320R1023

Includes: TH6320R1004 wireless programmable FocusPRO thermostat and THM4000R1000 adapter

1

4. TH6320R1004

Wireless thermostats for zones 3 and 4 (not needed for 2 zone system)

0–2

5. Appropriate zone dampers and by-pass damper for the application

 

Option C: 2–4 Zones

Table 3. Dual Fuel. 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace

 

 

 

Parts list

Description

Quantity

1. HZ432K zone panel kit

Includes: HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042

1

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM. (Different kits can also include accessories such

1

3. YTH6320R1023

Includes: TH6320R1004 wireless programmable FocusPRO thermostat and

1

4. TH6320R1004

Wireless thermostats for zones 3 and 4 (not needed for 2 zone system)

0–2

5. C7089R1013

Wireless outdoor sensor for dual fuel changeover

1

6. Appropriate zone dampers and by-pass damper for the application

See Fig. 1 below for basic wiring.

Honeywell Home RedLINK FocusPRO Wiring

Option D: More Than 4 Zones (Cannot use THM4000R Wireless Adapter)

Table 4. 1–3 Stage Furnace + 1–2 Stage Cooling, Heat-Pump with 1–2 Compressor Stages + Auxiliary Heat, or 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace (Dual Fuel).

Parts list

Description

Quantity

1. HZ432K zone panel kit

Includes: HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer

1

2. TAZ-4H

Add-A-Zone panel

1 per each additional 4 zones

3. AT140A1042

40VA transformer

1 per TAZ-4H panel

4. YTHX9421R

Prestige IAQ kit with Thermostat & EIM. (Different kits can also include accessories such as a RedLINK Internet gateway.)

1

5. YTH6320R1001

Wireless FocusPRO and EIM kit

 

1 for each zone other than the Prestige zone

6. Appropriate zone

dampers and by-pass damper for the application

 

7. C7089U1006 Wired outdoor sensor (required for dual fuel applications only)

See Fig. 2 below for basic wiring

Honeywell Home RedLINK FocusPRO Wiring2

NO IAQ EQUIPMENT OR ECONOMIZER CONTROL

For any of the 2-4 zone applications listed in this document that do not need to control a Humidifier, Dehumidifier, Ventilator, economizer, or Remote Indoor Sensor, you can eliminate the THM5421R1021. You can either enroll the Prestige IAQ thermostat to the THM4000R1000 wireless adapter that is included in the YTH6320R1023 kit or use another TH6320R1004 thermostat for zone 1 in place of the Prestige IAQ. When a TAZ-4H is used for systems over 4 zones, you cannot use a THM4000R1000.

See Fig. 3 below for basic wiring

Honeywell Home RedLINK FocusPRO Wiring3

ALL PRESTIGE THERMOSTATS WITHOUT IAQ CONTROL

Option E: 2–3 Zones (If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need separate EIM for Each Stat).

Table 5. 1–2 Stage Furnace + 1–2 Stage Cooling or Single Stage Heat-Pump + Electric Heat-Strips for Auxiliary Heat. Not Dual Fuel.

Parts list

Description

Quantity

1. HZ322K zone panel kit

Includes: HZ322 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer

1

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually zone 1). Different kits can also include accessories such as a RedLINK Internet gateway

1

3. THX9421R5021

Prestige without EIM for zones 2–3

1–2

4. THM4000R1000

Wireless adapter for zone 2–3 Prestige IAQ thermostats not controlling IAQ equipment or using an indoor sensor

1

5. Appropriate zone dampers and by-pass damper for the application

 

Option F: 2–4 Zones (If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need Separate EIM for Each Stat).

Table 6. 1–3 Stage Furnace + 1–2 Stage Cooling, or 1–2 Stage Heat-Pump + Electric Heat-Strips for Auxiliary Heat.

Parts list

Description

Quantity

1. HZ432K zone panel kit

Includes: HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer

1

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually zone 1). Different kits can also include accessories such as a RedLINK Internet gateway

1

3. THX9421R5021

Prestige without EIM for zones 2–4

1–3

4. THM4000R1000

Wireless adapter for zone 2–4 Prestige IAQ thermostats not controlling IAQ equipment or using an indoor sensor

1

5. Appropriate zone dampers and by-pass damper for the application.

 

Option G: 2–4 Zones (If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need Separate EIM for Each Stat).

Table 7. Dual Fuel. 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace.

 

Parts list

Description

Quantity

1. HZ432K zone panel kit.

Includes: HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer

1

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually zone 1). Different kits can also include accessories such as a RedLINK Internet gateway

1

3. THX9421R5021

Prestige without EIM for zones 2–4

1–3

4. THM4000R1000

Wireless adapter for zone 2-4 Prestige IAQ thermostats not controlling IAQ equipment or using an indoor sensor

1

5. C7089R1013

Wireless outdoor sensor

1

6. Appropriate zone dampers and by-pass damper for the application

 

See Fig. 4 below for basic wiring.

Honeywell Home RedLINK FocusPRO Wiring4

Option H: More Than 4 zones (Cannot Use THM4000R Wireless Adapter)

Table 8. 1–3 Stage Furnace + 1–2 Stage Cooling, Heat-Pump with 1–2 Compressor Stages + Auxiliary Heat, or 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace (Dual Fuel).

 

 

 

Parts list

Description

Quantity

1. HZ432K zone panel kit

Includes HZ432 zone panel, C7735A1000 discharge sensor, and

1

2. TAZ-4H

Add-A-Zone panel

1 per each additional 4 zones

3. AT140A1042

40VA transformer

1 per TAZ-4H panel

4. YTHX9421R

Prestige IAQ thermostat kit with EIM

1 for each zone

RedLINK VisionPRO instead of Prestige

For any of the A–F applications listed, you could replace the Prestige IAQ thermostats with TH8321R1001 RedLINK VisionPRO models. When the RedLINK VisionPRO models are used, you can link to the THM5421R1021 or THM4000R1000 (same as Prestige) or wire directly from the thermostat sub-base to the zone connection on the zone panel if wires are available.

See Fig. 5 below for basic wiring.

Honeywell Home RedLINK FocusPRO Wiring5

No IAQ Equipment

Any of the above listed 2-4 zone applications that do not need to control a Humidifier, Dehumidifier, Ventilator, Economizer or Remote Indoor Sensor can eliminate the THM5421R1021. You can enroll all Prestige IAQ or RedLINK VisionPRO thermostats to the THM4000R1000 wireless adapter. When a TAZ-4H is used for systems over 4 zone you cannot use a THM4000R1000.

See Fig. 6 below for basic wiring

Honeywell Home RedLINK FocusPRO Wiring6

EIM to Zone Panel Wiring Diagrams

EIM to Zone Panel Wiring Diagrams1

Fig. 7. Gas furnace and AC

EIM to Zone Panel Wiring Diagrams2

Fig. 8. Heat pump with 1-stage compressor and electric strips.

EIM to Zone Panel Wiring Diagrams3

Fig. 9. Heat pump with 2-stage compressor and electric strips.

EIM to Zone Panel Wiring Diagrams4

Fig. 10. Dual fuel heat pump.

Readmore and Download Honeywell Home RedLINK FocusPRO Thermostats Manual

Title

: Honeywell Home RedLINK FocusPRO Thermostats Manual

Format

: PDF

Pages

: 11 Pages

Language

: English

File Size

: 2.1 MB